Commission Delegated Regulation (EU) 2016/364 of 1 July 2015 on the classificatio... (32016R0364)
EU - Rechtsakte: 13 Industrial policy and internal market
15.3.2016   
EN
Official Journal of the European Union
L 68/4

COMMISSION DELEGATED REGULATION (EU) 2016/364

of 1 July 2015

on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council

(Text with EEA relevance)

THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions for the marketing of construction products and repealing Council Directive 89/106/EEC(1), and in particular Article 27(1) thereof,
Whereas:
(1) A system for classifying the performance of construction products with regard to their reaction to fire was adopted by Commission Decision 2000/147/EC(2). It was based on a harmonised solution of assessing this performance and classifying the results of these assessments.
(2) Decision 2000/147/EC provides several classes of reaction to fire performance. In addition, it contains classes F, F
FL
, F
L
and F
ca
, which are defined as ‘no performance determined’.
(3) In accordance with Article 2(7) of Regulation (EU) No 305/2011, a class means a range of levels, delimited by a minimum and a maximum value of performance. Classes defined as ‘no performance determined’ do not correspond to this definition and thus cannot be incorporated in a classification system under Regulation (EU) No 305/2011.
(4) The use of ‘no performance determined’ in the context of drawing up the declaration of performance is provided in Article 6(3)(f) of Regulation (EU) No 305/2011.
(5) In order to enable the manufacturers to declare lower reaction to fire performance than that covered by classes E, E
FL
, E
L
and E
ca
, it is necessary to change the classification criteria of classes F, F
FL
, F
L
and F
ca
accordingly.
(6) It is therefore necessary to replace the classes F, F
FL
, F
L
and F
ca
provided in Decision 2000/147/EC with new classes for products not reaching at least the reaction to fire performance under the classes E, E
FL
, E
L
and E
ca
.
(7) Decision 2000/147/EC has been amended several times and further amendments to that Decision are necessary. In the interests of clarity and rationality that decision should therefore be repealed and replaced,
HAS ADOPTED THIS REGULATION:

Article 1

When the intended use of a construction product is such that the product may contribute to the generation and spread of fire and smoke within the room or area of origin or beyond, the performance of the product in relation to its reaction to fire shall be classified in accordance with the classification system set out in the Annex.

Article 2

Decision 2000/147/EC is repealed.
References to the repealed Decision shall be construed as references to this Regulation.

Article 3

This Regulation shall enter into force on the twentieth day following that of its publication in the
Official Journal of the European Union
.
This Regulation shall be binding in its entirety and directly applicable in all Member States.
Done at Brussels, 1 July 2015.
For the Commission
The President
Jean-Claude JUNCKER
(1)  
OJ L 88, 4.4.2011, p. 5
.
(2)  Commission Decision 2000/147/EC of 8 February 2000 implementing Council Directive 89/106/EEC as regards the classification of the reaction to fire performance of construction products (
OJ L 50, 23.2.2000, p. 14
).

ANNEX

Classes of reaction to fire performance

1.1.
For the purposes of Tables 1 to 4 the following symbols(1) apply:
(1)   
‘ΔΤ’
— temperature rise;
(2)   
‘Δm’
— mass loss;
(3)   
‘t
f
— duration of flaming;
(4)   
‘PCS’
— gross calorific potential;
(5)   
‘LFS’
— lateral flame spread;
(6)   
‘SMOGRA’
— smoke growth rate.
1.2.
For the purposes of Tables 1, 2 and 3 the following symbols(1) apply:
(1)   
‘FIGRA’
— fire growth rate;
(2)   
‘THR’
— total heat release;
(3)   
‘TSP’
— total smoke production;
(4)   
‘Fs’
— flame spread.
1.3.
For the purposes of Table 4 the following symbols and test parameters apply:
(1)   
‘HRR
sm30
, kW’
— heat release rate averaged by a 30-s sliding average;
(2)   
‘SPR
sm60
, m
2
/s’
— smoke production rate averaged by a 60-s sliding average;
(3)   
‘Peak HRR, kW’
— maximum of HRR
sm30
between test start and end of test, excluded contribution from ignition source;
(4)   
‘Peak SPR, m
2
/s’
— maximum of SPR
sm60
between test start and end of test;
(5)   
‘THR
1200
, MJ’
— total heat release (HRR
sm30
) from test start until end of test, excluded contribution from ignition source;
(6)   
‘TSP
1200
, m
2
— total smoke production (HRR
sm60
) from test start until end of test;
(7)   
‘FIGRA, W/s’
— fire growth rate index defined as the highest value of the quotient between HRR
sm30
excluding the contribution of ignition source and time. Threshold values HRR
sm30
 = 3 kW and THR = 0,4 MJ;
(8)   
‘FS’
— flame spread (damaged length);
(9)   
‘H’
— flame spread.
2.
For the purposes of Tables 1 to 4 the following definitions apply:
(1) ‘material’ means a single basic substance or uniformly dispersed mixture of substances;
(2) ‘homogeneous product’ means a product consisting of a single material, having uniform density and composition throughout the product;
(3) ‘non-homogeneous product’ means a product that does not satisfy the requirements of a homogeneous product and that is composed of one or more components, substantial and/or non-substantial;
(4) ‘substantial component’ means a material that constitutes a significant part of a non-homogeneous product; a layer with a mass per unit area ≥ 1,0 kg/m
2
or a thickness ≥ 1,0 mm is considered to be a substantial component;
(5) ‘non-substantial component’ means a material that does not constitute a significant part of a non-homogeneous product; a layer with a mass per unit area < 1,0 kg/m
2
and a thickness < 1,0 mm is considered to be a non-substantial component;
(6) ‘internal non-substantial component’ means a non-substantial component that is covered on both sides by at least one substantial component;
(7) ‘external non-substantial component’ means a non-substantial component that is not covered on one side by a substantial component.
Two or more non-substantial layers that are adjacent to each other, where there are no substantial components in between the layers, shall be considered as one non-substantial component and shall, therefore, be classified in accordance with the criteria for a layer that is a non-substantial component.
Table 1
Classes of reaction to fire performance for construction products excluding floorings, linear pipe thermal insulation products, and electric cables

Class

Test method(s)

Classification criteria

Additional classification

A1

EN ISO 1182(2);

and

ΔΤ ≤ 30 °C; and

Δm ≤ 50 %; and

tf = 0 (i.e. no sustained flaming)

 

EN ISO 1716

PCS ≤ 2,0 MJkg– 1 (2); and

PCS ≤ 2,0 MJkg– 1 (3) (1); and

PCS ≤ 1,4 MJm– 2 (4); and

PCS ≤ 2,0 MJkg– 1 (5)

 

A2

EN ISO 1182(2);

or

ΔΤ ≤ 50 °C; and

Δm ≤ 50 %; and

tf ≤ 20 s

 

EN ISO 1716;

and

PCS ≤ 3,0 MJkg– 1 (2); and

PCS ≤ 4,0 MJm– 2 (3); and

PCS ≤ 4,0 MJm– 2 (4); and

PCS ≤ 3,0 MJkg– 1 (5)

 

EN 13823 (SBI)

FIGRA ≤ 120 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 7,5 MJ

Smoke production(6); and

Flaming droplets/particles(7)

B

EN 13823 (SBI);

and

FIGRA ≤ 120 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 7,5 MJ

Smoke production(6); and

Flaming droplets/particles(7)

EN ISO 11925-2(9):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

C

EN 13823 (SBI);

and

FIGRA ≤ 250 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 15 MJ

Smoke production(6); and

Flaming droplets/particles(7)

EN ISO 11925-2(9):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

D

EN 13823 (SBI);

and

FIGRA ≤ 750 Ws– 1

Smoke production(6); and

Flaming droplets/particles(7)

EN ISO 11925-2(9):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

E

EN ISO 11925-2(9):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

Flaming droplets/particles(8)

F

EN ISO 11925-2(9):

Exposure = 15 s

Fs > 150 mm within 20 s

 

Table 2
Classes of reaction to fire performance for floorings

Class

Test method(s)

Classification criteria

Additional classification

A1FL

EN ISO 1182(10);

and

ΔΤ ≤ 30 °C; and

Δm ≤ 50 %; and

tf = 0 (i.e. no sustained flaming)

 

EN ISO 1716

PCS ≤ 2,0 MJkg– 1 (10); and

PCS ≤ 2,0 MJkg– 1 (11); and

PCS ≤ 1,4 MJm– 2 (12); and

PCS ≤ 2,0 MJkg– 1 (13)

A2FL

EN ISO 1182(10);

or

ΔΤ ≤ 50 °C; and

Δm ≤ 50 %; and

tf ≤ 20 s

 

EN ISO 1716;

and

PCS ≤ 3,0 MJkg– 1 (10); and

PCS ≤ 4,0 MJm– 2 (11); and

PCS ≤ 4,0 MJm– 2 (12); and

PCS ≤ 3,0 MJkg– 1 (13)

EN ISO 9239-1(14)

Critical flux(15) ≥ 8,0 kWm– 2

Smoke production(16)

BFL

EN ISO 9239-1(14)

and

Critical flux(15) ≥ 8,0 kWm– 2

Smoke production(16)

EN ISO 11925-2(17):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

CFL

EN ISO 9239-1(14)

and

Critical flux(15) ≥ 4,5 kWm– 2

Smoke production(16)

EN ISO 11925-2(17):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

DFL

EN ISO 9239-1(14)

and

Critical flux(15) ≥ 3,0 kWm– 2

Smoke production(16)

EN ISO 11925-2(17):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

EFL

EN ISO 11925-2(17):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

 

FFL

EN ISO 11925-2(17):

Exposure = 15 s

Fs > 150 mm within 20 s

 

Table 3
Classes of reaction to fire performance for linear pipe insulation products

Class

Test method(s)

Classification criteria

Additional classification

A1L

EN ISO 1182(18);

and

ΔT ≤ 30 °C; and

Δm ≤ 50 %; and

tf = 0 (i.e. no sustained flaming)

 

EN ISO 1716

PCS ≤ 2,0 MJkg– 1 (18); and

PCS ≤ 2,0 MJkg– 1 (19); and

PCS ≤ 1,4 MJm– 2 (20); and

PCS ≤ 2,0 MJkg– 1 (21)

A2L

EN ISO 1182(18);

or

ΔT ≤ 50 °C; and

Δm ≤ 50 %; and tf ≤ 20 s

 

EN ISO 1716;

and

PCS ≤ 3,0 MJkg– 1 (18); and

PCS ≤ 4,0 MJm– 2 (19); and

PCS ≤ 4,0 MJm– 2 (20); and

PCS ≤ 3,0 MJkg– 1 (21)

EN 13823 (SBI)

FIGRA ≤ 270 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 7,5 MJ

Smoke production(22); and

Flaming droplets/particles(23)

BL

EN 13823 (SBI);

and

FIGRA ≤ 270 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 7,5 MJ

Smoke production(22); and

Flaming droplets/particles(23)

EN ISO 11925-2(25):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

CL

EN 13823 (SBI);

and

FIGRA ≤ 460 Ws– 1; and

LFS < edge of specimen; and

THR600s ≤ 15 MJ

Smoke production(22); and

Flaming droplets/particles(23)

EN ISO 11925-2(25):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

DL

EN 13823 (SBI);

and

FIGRA ≤ 2 100 Ws– 1

THR600s ≤ 100 MJ

Smoke production(22); and

Flaming droplets/particles(23)

EN ISO 11925-2(25):

Exposure = 30 s

Fs ≤ 150 mm within 60 s

EL

EN ISO 11925-2(25):

Exposure = 15 s

Fs ≤ 150 mm within 20 s

Flaming droplets/particles(24)

FL

EN ISO 11925-2(25):

Exposure = 15 s

Fs > 150mm within 20 s

 

Table 4
Classes of reaction to fire performance for electric cables

Class

Test method(s)

Classification criteria

Additional classification

Aca

EN ISO 1716

PCS ≤ 2,0 MJ/kg(26)

 

B1ca

EN 50399 (30 kW flame source)

and

FS ≤ 1,75 m and

THR1200s ≤ 10 MJ and

Peak HRR ≤ 20 kW and

FIGRA ≤ 120 Ws– 1

Smoke production(27) (30) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29)

EN 60332-1-2

H ≤ 425 mm

B2ca

EN 50399 (20,5 kW flame source)

and

FS ≤ 1,5 m; and

THR1200s ≤ 15 MJ; and

Peak HRR ≤ 30 kW; and

FIGRA ≤ 150 Ws– 1

Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29)

EN 60332-1-2

H ≤ 425 mm

Cca

EN 50399 (20,5 kW flame source)

and

FS ≤ 2,0 m; and

THR1200s ≤ 30 MJ; and

Peak HRR ≤ 60 kW; and

FIGRA ≤ 300 Ws– 1

Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29)

EN 60332-1-2

H ≤ 425 mm

Dca

EN 50399 (20,5 kW flame source)

and

THR1200s ≤ 70 MJ; and

Peak HRR ≤ 400 kW; and

FIGRA ≤ 1 300 Ws– 1

Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29)

EN 60332-1-2

H ≤ 425 mm

Eca

EN 60332-1-2

H ≤ 425 mm

 

Fca

EN 60332-1-2

H > 425 mm

 

(1)  The characteristics are defined with respect to the appropriate test method.
(2)  For homogeneous products and substantial components of non-homogeneous products.
(3)  For any external non-substantial component of non-homogeneous products.
(1)  
(
2a
)
Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm
– 2
, provided that the product satisfies the following criteria of EN 13823(SBI): FIGRA ≤ 20 Ws
– 1
;
and
LFS < edge of specimen;
and
THR
600s
≤ 4,0 MJ;
and
s1;
and
d0.
(4)  For any internal non-substantial component of non-homogeneous products.
(5)  For the product as a whole.
(6)  
s1
= SMOGRA ≤ 30m
2
s
– 2
and
TSP
600s
≤ 50m
2
;
s2
= SMOGRA ≤ 180m
2
s
– 2
and
TSP
600s
≤ 200m
2
;
s3
= not s1 or s2.
(7)  
d0
= No flaming droplets/particles in EN 13823 (SBI) within 600s;
d1
= No flaming droplets/particles persisting longer than 10s in EN 13823 (SBI) within 600s;
d2
= not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
(8)  No ignition of the paper = no additional classification; Ignition of the paper =
d2
classification.
(9)  Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
(10)  For homogeneous products and substantial components of non-homogeneous products.
(11)  For any external non-substantial component of non-homogeneous products.
(12)  For any internal non-substantial component of non-homogeneous products.
(13)  For the product as a whole.
(14)  Test duration = 30 minutes.
(15)  Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes, whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame).
(16)  
s1
= Smoke ≤ 750 %.min;
s2
= not s1.
(17)  Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
(18)  For homogeneous products and substantial components of non-homogeneous products.
(19)  For any external non-substantial component of non-homogeneous products.
(20)  For any internal non-substantial component of non-homogeneous products.
(21)  For the product as a whole.
(22)  
s1
= SMOGRA ≤ 105 m
2
s
– 2
and
TSP
600s
≤ 250 m
2
;
s2
= SMOGRA ≤ 580 m
2
s
– 2
and
TSP
600s
≤ 1 600 m
2
;
s3
= not s1 or s2.
(23)  
d0
= No flaming droplets/particles in EN13823 (SBI) within 600s;
d1
= No flaming droplets/particles persisting longer than 10s in EN13823 (SBI) within 600s;
d2
= not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
(24)  No ignition of the paper = no additional classification; Ignition of the paper =
d2
classification.
(25)  Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.
(26)  For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product.
(27)  
s1
= TSP
1200
≤ 50 m
2
and
Peak SPR ≤ 0,25 m
2
/s
s1a
=
s1
and transmittance in accordance with EN 61034-2 ≥ 80 %
s1b
=
s1
and transmittance in accordance with EN 61034-2 ≥ 60 % < 80 %
s2
= TSP
1200
≤ 400 m
2
and
Peak SPR ≤ 1,5 m
2
/s
s3
= not s1 or s2
(28)  
d0
= No flaming droplets/particles within 1 200 s;
d1
= No flaming droplets/particles persisting longer than 10 s within 1 200 s;
d2
= not
d0
or
d1
.
(29)  EN 60754-2:
a1
= conductivity < 2,5 μS/mm
and
pH > 4,3;
a2
= conductivity < 10 μS/mm
and
pH > 4,3;
a3
= not
a1
or
a2
.
(30)  The smoke class declared for class B1
ca
cables must originate from the EN 50399 test (30 kW flame source).
(31)  The smoke class declared for class B2
ca
, C
ca
, D
ca
cables must originate from the EN 50399 test (20,5 kW flame source).
Markierungen
Leseansicht