COMMISSION DELEGATED REGULATION (EU) 2016/364
of 1 July 2015
on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council
(Text with EEA relevance)
Article 1
Article 2
Article 3
ANNEX
Classes of reaction to fire performance
Class |
Test method(s) |
Classification criteria |
Additional classification |
A1 |
EN ISO 1182(2); and |
ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) |
|
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1 (2); and PCS ≤ 2,0 MJkg– 1 (3) (1); and PCS ≤ 1,4 MJm– 2 (4); and PCS ≤ 2,0 MJkg– 1 (5) |
|
|
A2 |
EN ISO 1182(2); or |
ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s |
|
EN ISO 1716; and |
PCS ≤ 3,0 MJkg– 1 (2); and PCS ≤ 4,0 MJm– 2 (3); and PCS ≤ 4,0 MJm– 2 (4); and PCS ≤ 3,0 MJkg– 1 (5) |
|
|
EN 13823 (SBI) |
FIGRA ≤ 120 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ |
Smoke production(6); and Flaming droplets/particles(7) |
|
B |
EN 13823 (SBI); and |
FIGRA ≤ 120 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ |
Smoke production(6); and Flaming droplets/particles(7) |
EN ISO 11925-2(9): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
C |
EN 13823 (SBI); and |
FIGRA ≤ 250 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 15 MJ |
Smoke production(6); and Flaming droplets/particles(7) |
EN ISO 11925-2(9): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
D |
EN 13823 (SBI); and |
FIGRA ≤ 750 Ws– 1 |
Smoke production(6); and Flaming droplets/particles(7) |
EN ISO 11925-2(9): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
E |
EN ISO 11925-2(9): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
Flaming droplets/particles(8) |
F |
EN ISO 11925-2(9): Exposure = 15 s |
Fs > 150 mm within 20 s |
|
Class |
Test method(s) |
Classification criteria |
Additional classification |
A1FL |
EN ISO 1182(10); and |
ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) |
|
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1 (10); and PCS ≤ 2,0 MJkg– 1 (11); and PCS ≤ 1,4 MJm– 2 (12); and PCS ≤ 2,0 MJkg– 1 (13) |
||
A2FL |
EN ISO 1182(10); or |
ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s |
|
EN ISO 1716; and |
PCS ≤ 3,0 MJkg– 1 (10); and PCS ≤ 4,0 MJm– 2 (11); and PCS ≤ 4,0 MJm– 2 (12); and PCS ≤ 3,0 MJkg– 1 (13) |
||
EN ISO 9239-1(14) |
Critical flux(15) ≥ 8,0 kWm– 2 |
Smoke production(16) |
|
BFL |
EN ISO 9239-1(14) and |
Critical flux(15) ≥ 8,0 kWm– 2 |
Smoke production(16) |
EN ISO 11925-2(17): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
||
CFL |
EN ISO 9239-1(14) and |
Critical flux(15) ≥ 4,5 kWm– 2 |
Smoke production(16) |
EN ISO 11925-2(17): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
||
DFL |
EN ISO 9239-1(14) and |
Critical flux(15) ≥ 3,0 kWm– 2 |
Smoke production(16) |
EN ISO 11925-2(17): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
||
EFL |
EN ISO 11925-2(17): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
|
FFL |
EN ISO 11925-2(17): Exposure = 15 s |
Fs > 150 mm within 20 s |
|
Class |
Test method(s) |
Classification criteria |
Additional classification |
A1L |
EN ISO 1182(18); and |
ΔT ≤ 30 °C; and Δm ≤ 50 %; and tf = 0 (i.e. no sustained flaming) |
|
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1 (18); and PCS ≤ 2,0 MJkg– 1 (19); and PCS ≤ 1,4 MJm– 2 (20); and PCS ≤ 2,0 MJkg– 1 (21) |
||
A2L |
EN ISO 1182(18); or |
ΔT ≤ 50 °C; and Δm ≤ 50 %; and tf ≤ 20 s |
|
EN ISO 1716; and |
PCS ≤ 3,0 MJkg– 1 (18); and PCS ≤ 4,0 MJm– 2 (19); and PCS ≤ 4,0 MJm– 2 (20); and PCS ≤ 3,0 MJkg– 1 (21) |
||
EN 13823 (SBI) |
FIGRA ≤ 270 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ |
Smoke production(22); and Flaming droplets/particles(23) |
|
BL |
EN 13823 (SBI); and |
FIGRA ≤ 270 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 7,5 MJ |
Smoke production(22); and Flaming droplets/particles(23) |
EN ISO 11925-2(25): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
CL |
EN 13823 (SBI); and |
FIGRA ≤ 460 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 15 MJ |
Smoke production(22); and Flaming droplets/particles(23) |
EN ISO 11925-2(25): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
DL |
EN 13823 (SBI); and |
FIGRA ≤ 2 100 Ws– 1 THR600s ≤ 100 MJ |
Smoke production(22); and Flaming droplets/particles(23) |
EN ISO 11925-2(25): Exposure = 30 s |
Fs ≤ 150 mm within 60 s |
||
EL |
EN ISO 11925-2(25): Exposure = 15 s |
Fs ≤ 150 mm within 20 s |
Flaming droplets/particles(24) |
FL |
EN ISO 11925-2(25): Exposure = 15 s |
Fs > 150mm within 20 s |
|
Class |
Test method(s) |
Classification criteria |
Additional classification |
Aca |
EN ISO 1716 |
PCS ≤ 2,0 MJ/kg(26) |
|
B1ca |
EN 50399 (30 kW flame source) and |
FS ≤ 1,75 m and THR1200s ≤ 10 MJ and Peak HRR ≤ 20 kW and FIGRA ≤ 120 Ws– 1 |
Smoke production(27) (30) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29) |
EN 60332-1-2 |
H ≤ 425 mm |
||
B2ca |
EN 50399 (20,5 kW flame source) and |
FS ≤ 1,5 m; and THR1200s ≤ 15 MJ; and Peak HRR ≤ 30 kW; and FIGRA ≤ 150 Ws– 1 |
Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29) |
EN 60332-1-2 |
H ≤ 425 mm |
||
Cca |
EN 50399 (20,5 kW flame source) and |
FS ≤ 2,0 m; and THR1200s ≤ 30 MJ; and Peak HRR ≤ 60 kW; and FIGRA ≤ 300 Ws– 1 |
Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29) |
EN 60332-1-2 |
H ≤ 425 mm |
||
Dca |
EN 50399 (20,5 kW flame source) and |
THR1200s ≤ 70 MJ; and Peak HRR ≤ 400 kW; and FIGRA ≤ 1 300 Ws– 1 |
Smoke production(27) (31) and Flaming droplets/particles(28) and Acidity (pH and conductivity)(29) |
EN 60332-1-2 |
H ≤ 425 mm |
||
Eca |
EN 60332-1-2 |
H ≤ 425 mm |
|
Fca |
EN 60332-1-2 |
H > 425 mm |
|